The medical gas pipeline system (MGPS) is one of the few hospital systems that patients' lives directly depend on, minute by minute. It carries oxygen, medical air and vacuum — and in OTs nitrous oxide and anaesthetic gas scavenging — from a central source to every bed that needs it. The pandemic showed how quickly a weak oxygen system becomes a crisis.
This guide explains how an MGPS is put together, how to choose the oxygen source, how outlets are planned, and how the system is tested before it goes live. It complements our PSA oxygen plant guide and hospital MEP guide.
In this guide ▾
- Design to a recognised standard: MGPS in India is designed to IS/ISO 7396-1, with HTM 02-01 and NFPA 99 widely used as references.
- Always have a backup: a secondary source, typically a cylinder manifold, is a standard requirement alongside the primary source.
- Liquid medical oxygen needs a PESO licence for the storage tank, plus a safe, open site and a third-party supply contract.
- Zone valves and alarms let staff isolate one area without shutting down the hospital, and warn them before pressure fails.
- Test everything before patients connect: pressure, leak, cross-connection and purity tests.
How a medical gas pipeline system works
A central plant supplies each gas into a copper pipeline network cleaned for oxygen service. The network is divided into zones — each ward, ICU and OT — with valve boxes that can isolate one zone without affecting others, and alarms that warn of pressure problems. At the bedside, gas-specific terminal units make it physically impossible to connect a device to the wrong gas.
| Gas / service | Main uses |
|---|---|
| Oxygen | Wards, ICU, OT, emergency, NICU |
| Medical air | Ventilators, nebulisation, anaesthesia |
| Medical vacuum | Suction in wards, ICU, OT |
| Nitrous oxide | Anaesthesia in OT and labour rooms |
| AGSS | Scavenging waste anaesthetic gas from OTs |
| Carbon dioxide | Laparoscopic surgery insufflation |
class="attachment-full size-full wp-image-8029" alt="Medical gas pipeline system diagram: source, main pipeline, zone valve boxes, area alarms, terminal outlets" srcset="https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow.png 1200w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-300x110.png 300w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-1024x375.png 1024w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-768x282.png 768w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-150x55.png 150w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-480x176.png 480w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-24x9.png 24w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-36x13.png 36w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-system-flow-48x18.png 48w" sizes="(max-width:767px) 480px, (max-width:1200px) 100vw, 1200px" /> Planning outlets by area
Outlet numbers depend on the type of care in each area. ICU beds and operation theatres need multiple oxygen, air and vacuum points; general ward beds need fewer. The final numbers and pipe sizes come from a design calculation of flow and diversity, done to the chosen standard. See our ICU design guide and OT design guide for how outlets fit into bed-head and pendant layouts.
class="attachment-full size-full wp-image-8027" alt="Medical gas outlets per bed in hospital: oxygen, medical air and vacuum in wards, ICU, OT, recovery and emergency" srcset="https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets.png 1200w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-300x154.png 300w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-1024x524.png 1024w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-768x393.png 768w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-147x75.png 147w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-480x246.png 480w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-24x12.png 24w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-36x18.png 36w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-gases-and-outlets-48x25.png 48w" sizes="(max-width:767px) 480px, (max-width:1200px) 100vw, 1200px" /> Choosing the oxygen source
Liquid medical oxygen (LMO) is stored in a cryogenic tank refilled by tanker and flows into the pipeline without needing electricity; the tank needs a PESO licence, a safe open space and a supply contract. A PSA plant generates oxygen on site from air and depends on reliable power. Cylinder manifolds suit small units and are the usual automatic backup for larger hospitals.
class="attachment-full size-full wp-image-8028" alt="Hospital oxygen source comparison: liquid medical oxygen tank vs PSA oxygen plant vs cylinder manifold" srcset="https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources.png 1200w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-300x146.png 300w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-1024x498.png 1024w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-768x374.png 768w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-150x73.png 150w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-480x234.png 480w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-24x12.png 24w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-36x18.png 36w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-oxygen-sources-48x23.png 48w" sizes="(max-width:767px) 480px, (max-width:1200px) 100vw, 1200px" /> An LMO tank needs a safe, open, unhindered location with tanker access and clearances. Leaving it to the end often means losing parking or redesigning the site, so reserve the space when the plot is first planned.
Commissioning and safety checks
No pipeline should go live until it has been pressure and leak tested section by section, checked for cross-connections at every outlet and tested for gas purity. The alarms, zone valves and automatic backup changeover must be demonstrated, and staff trained on emergency isolation. These checks are part of our civil, MEP and fire turnkey services.
class="attachment-full size-full wp-image-8025" alt="Medical gas pipeline commissioning checklist: pressure test, cross connection test, purity test, zone valves, alarms, backup" srcset="https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist.png 1200w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-300x150.png 300w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-1024x510.png 1024w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-768x383.png 768w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-150x75.png 150w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-480x239.png 480w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-24x12.png 24w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-36x18.png 36w, https://www.hospertz.com/wp-content/uploads/2026/11/medical-gas-pipeline-system-mgps-hospital-design-india-commissioning-checklist-48x24.png 48w" sizes="(max-width:767px) 480px, (max-width:1200px) 100vw, 1200px" /> Designing or upgrading your hospital's medical gas system?
Hospertz designs and delivers MGPS as part of turnkey MEP, from source selection to commissioning.
Frequently asked questions
What is MGPS in a hospital?
MGPS stands for medical gas pipeline system: the central network that delivers oxygen, medical air, vacuum and other medical gases from a source plant to terminal outlets at beds, OTs and other clinical areas.
Which standard is used for medical gas pipelines in India?
MGPS in India is designed to IS/ISO 7396-1, the standard for pipeline systems for compressed medical gases and vacuum. HTM 02-01 and NFPA 99 are also widely used as design references.
Does a liquid oxygen tank need a licence?
Yes. A liquid medical oxygen storage tank at a hospital requires a licence from PESO (Petroleum and Explosives Safety Organisation), along with a suitable safe site and a supply arrangement.
How many oxygen outlets does an ICU bed need?
ICU beds are commonly planned with two oxygen outlets, one or two medical air outlets and two vacuum outlets, but the final number should follow the design standard and the hospital's clinical requirements.
Is a backup oxygen supply mandatory?
Yes, MGPS norms and standards call for a secondary or backup source, ideally a cylinder manifold that switches over automatically if the primary source fails.
Get your medical gas system designed right
Source selection, outlet planning, installation and commissioning by Hospertz MEP engineers.
Keep reading
Outlet numbers and source choices shown are typical planning guidance; final design must follow the applicable standard and a project-specific calculation. This article is general information, not engineering advice.